How to Interpolate Steam Tables (Saturated and Superheated)

To interpolate a steam table, find the two rows on either side of your value, then assume the property changes in a straight line between them:

y = y1 + (x − x1) × (y2 − y1) / (x2 − x1)

Here x is the property you know (temperature or pressure), and y is the property you want (enthalpy, specific volume, entropy and so on). For the row spacing used in standard tables, this gives enthalpy to within a few tenths of a kJ/kg. You can run every step below in our linear interpolation calculator.

This guide works through each type of steam table lookup you will meet in a thermodynamics course: saturated tables by temperature, saturated tables by pressure, wet steam with a quality, and superheated steam. It also shows how far off each result is.

Where the numbers in this guide come from

All table values below come from the IAPWS-IF97 formulation, the industrial standard for water and steam published by the International Association for the Properties of Water and Steam. They are rounded the way printed tables round them: enthalpy to 0.1 kJ/kg and specific volume to four or five significant digits. Your textbook may differ in the last digit, because some books use the older IAPWS-95 data or round differently. The method does not change.

For each example we also show the exact IF97 value at the target, so you can see how much error the straight-line assumption adds.

Step by step: how to interpolate any steam table

  1. Pick the right table. Below the saturation temperature for your pressure, you have compressed liquid. Above it, you have superheated vapor. Exactly at saturation, with liquid and vapor present together, you use the saturated table.
  2. Find the bracketing rows. These are the two table entries just below and just above your known value.
  3. Write down both values of the property you need, from the same column.
  4. Compute the fraction (x − x1) / (x2 − x1). This tells you how far your point lies between the two rows, from 0 to 1.
  5. Apply the fraction to the property change: y = y1 + fraction × (y2 − y1).
  6. Sanity check. The answer must lie between y1 and y2. If it does not, you used the wrong row or mixed up columns.

Example 1: saturated steam table by temperature

Problem: Find the saturated vapor enthalpy hg, the liquid enthalpy hf and the enthalpy of vaporization hfg at 152 °C.

The temperature table lists 150 °C and 155 °C:

T (°C) Psat (kPa) hf (kJ/kg) hfg (kJ/kg) hg (kJ/kg) vg (m³/kg)
150 476.10 632.3 2113.7 2745.9 0.3925
155 543.42 653.9 2097.9 2751.8 0.3465

Fraction: (152 − 150) / (155 − 150) = 2 / 5 = 0.4

hg: 2745.9 + 0.4 × (2751.8 − 2745.9) = 2745.9 + 0.4 × 5.9 = 2748.26 kJ/kg

hf: 632.3 + 0.4 × (653.9 − 632.3) = 632.3 + 0.4 × 21.6 = 640.94 kJ/kg

hfg: 2113.7 + 0.4 × (2097.9 − 2113.7) = 2113.7 − 6.32 = 2107.38 kJ/kg

How accurate is it? The exact IF97 values at 152 °C are hg = 2748.3, hf = 640.9 and hfg = 2107.4 kJ/kg. All three interpolated results match to within 0.04 kJ/kg, which is smaller than the table’s own rounding.

Not every column is this well behaved

Interpolating the same two rows for saturation pressure gives 476.10 + 0.4 × 67.32 = 503.03 kPa. The true value is 502.18 kPa, so the error is about 0.85 kPa. Specific volume does a little worse in relative terms: the interpolated vg is 0.3741 m³/kg against a true 0.37327 m³/kg, about 0.2 percent high.

The reason is curvature. Saturation pressure rises roughly exponentially with temperature, and vapor volume falls in a curve, so a straight chord between two rows sits slightly above the real curve. Enthalpy is close to linear over a 5 °C step, so it interpolates almost perfectly. For homework this level of error is acceptable. For design work, use closer table spacing or an IF97 property routine.

Check it with the calculator

Open the interpolation calculator and enter:

  • X1 = 150, Y1 = 2745.9
  • X2 = 155, Y2 = 2751.8
  • X3 = 152, and leave Y3 empty

Press Calculate. Y3 shows 2748.26, the hg found above.

Example 2: saturated steam table by pressure

Problem: Find the saturation temperature and hfg at 0.45 MPa (450 kPa). Your table lists 0.40 and 0.50 MPa.

P (MPa) Tsat (°C) hf (kJ/kg) hfg (kJ/kg) hg (kJ/kg)
0.40 143.61 604.7 2133.3 2738.1
0.50 151.84 640.2 2107.9 2748.1

Fraction: (0.45 − 0.40) / (0.50 − 0.40) = 0.5. This is the midpoint, so each answer is simply the average of the two rows.

  • Tsat = (143.61 + 151.84) / 2 = 147.73 °C (147.725 before rounding)
  • hf = (604.7 + 640.2) / 2 = 622.45 kJ/kg
  • hfg = (2133.3 + 2107.9) / 2 = 2120.6 kJ/kg
  • hg = (2738.1 + 2748.1) / 2 = 2743.1 kJ/kg

The exact IF97 values at 0.45 MPa are Tsat = 147.91 °C, hf = 623.2, hfg = 2120.2 and hg = 2743.4 kJ/kg. The errors are now a bit larger, about 0.2 °C and 0.75 kJ/kg on hf. Two things explain this: the pressure step is wide (a 25 percent change from 0.4 to 0.5 MPa), and temperature is a curved function of pressure. Many tables add a 0.45 MPa row for this reason. If yours has one, use it and skip the interpolation.

Example 3: wet steam with a quality

Wet steam is a liquid and vapor mixture. Its quality x is the mass fraction that is vapor. Any mixture property follows the same pattern:

h = hf + x × hfg

When the temperature or pressure falls between table rows, interpolate hf and hfg first, then apply the quality.

Problem: Steam at 152 °C has a quality of 0.85. Find its enthalpy.

From Example 1, hf = 640.94 kJ/kg and hfg = 2107.38 kJ/kg at 152 °C.

h = 640.94 + 0.85 × 2107.38 = 640.94 + 1791.27 = 2432.21 kJ/kg

The exact IF97 value is 2432.19 kJ/kg, which is effectively perfect.

Working backward: find the quality from enthalpy

Problem: A mixture at 0.45 MPa has h = 2400 kJ/kg. What is its quality?

From Example 2, hf = 622.45 and hfg = 2120.6 kJ/kg.

x = (h − hf) / hfg = (2400 − 622.45) / 2120.6 = 0.8382

So the mixture is about 83.8 percent vapor by mass. Check that h lies between hf and hg before you start. If h were greater than hg (2743.1 kJ/kg here), the steam would be superheated and you would need the superheated table instead.

Example 4: superheated steam table

Superheated tables are arranged in blocks, one per pressure, with temperature down the side. If your pressure matches one of the blocks, you only interpolate in temperature.

Problem: Find h, v and s for steam at 1.0 MPa and 325 °C.

T (°C) at 1.0 MPa v (m³/kg) h (kJ/kg) s (kJ/kg·K)
300 0.25798 3051.7 7.1247
350 0.28249 3158.2 7.3028

Fraction: (325 − 300) / (350 − 300) = 0.5

  • h = (3051.7 + 3158.2) / 2 = 3104.95 kJ/kg (exact IF97: 3105.0)
  • v = (0.25798 + 0.28249) / 2 = 0.27024 m³/kg (exact: 0.27030)
  • s = (7.1247 + 7.3028) / 2 = 7.21375 kJ/kg·K (exact: 7.2158)

Enthalpy and volume are excellent. Entropy is off by about 0.002, because entropy grows roughly with the logarithm of temperature and so curves slightly.

Calculator tip for specific volume: the calculator displays two decimal places, so a value like 0.27024 would show as 0.27. Convert to liters per kilogram first (multiply by 1000): enter Y1 = 258.0 and Y2 = 282.5 with X1 = 300, X2 = 350 and X3 = 325. You get 270.25 L/kg, which is 0.27025 m³/kg once divided back. The last digit differs from the hand result above only because the table values were rounded to 0.1 L/kg.

If your pressure is also between two blocks (for example 1.2 MPa and 325 °C), you need to interpolate twice. That case is covered in double interpolation.

How wide a gap is too wide?

Linear interpolation gets worse as the rows get further apart. As a test, take the 1.0 MPa superheated block and skip the middle row: interpolate between 200 °C (h = 2828.3) and 400 °C (h = 3264.4) to estimate h at 300 °C.

  • Interpolated: 3046.35 kJ/kg
  • True value: 3051.7 kJ/kg
  • Error: about 5.4 kJ/kg

That is more than 100 times worse than the 50 °C step in Example 4. Always use the two nearest rows, not just any two rows that bracket the value. Close to the saturation line, where properties curve sharply, take extra care even with close rows.

Common mistakes when interpolating steam tables

  • Using the wrong table. Compare your temperature with Tsat at your pressure before choosing saturated or superheated data.
  • Mixing columns. It is easy to read hf from one row and hg from the next. Write both rows out in full first, as in the tables above.
  • Interpolating hfg from hg alone. Interpolate hf and hfg (or hf and hg) separately, then combine them. Do not subtract values taken from different rows.
  • Rounding too early. Keep at least one more digit than the table through the intermediate steps, then round the final answer.
  • Extrapolating. If your value lies outside the table range, linear interpolation turns into extrapolation, and errors grow quickly. See linear extrapolation for when that is acceptable.
  • Mixing units. Some tables list pressure in kPa and others in MPa or bar. Convert everything to the same unit before computing the fraction.

Frequently asked questions

Is linear interpolation accurate enough for steam tables?

For enthalpy and internal energy with standard row spacing, yes. The errors in this guide were mostly below 0.1 kJ/kg, smaller than the table rounding. Pressure, specific volume and entropy curve more, so expect errors of a few tenths of a percent. This is accepted practice in thermodynamics courses and exams.

How do I interpolate when both temperature and pressure are between table values?

Interpolate in temperature at each of the two bracketing pressures, then interpolate those two results in pressure. This is called double interpolation, and our double interpolation guide works through a full superheated steam example. It is the same idea as bilinear interpolation.

How do I find temperature when I know enthalpy?

Swap the roles of the columns: treat enthalpy as the known x and temperature as the unknown y, and interpolate as usual. Our inverse interpolation article shows this with steam data and explains how to do it in the calculator.

Can I interpolate across the saturation line?

No. Properties jump at the phase change, so a straight line between a liquid row and a vapor row means nothing physically. Stay within one phase region, or use the quality method for mixtures.

Where can I get exact steam properties to check my work?

The NIST Chemistry WebBook fluid properties tool gives water and steam properties at any state point. It is a good way to check a homework answer.

Related guides

New to interpolation? Our step-by-step guide on how to interpolate covers the basic method with simple examples.

Soren Vance
Soren Vance

Soren Vance is the Director of Quantitative Analysis & Algorithms at Interpolation Calculator, where he leads the design and optimization of the company’s core interpolation engines and data processing frameworks.

With a master’s in Computational Mathematics and over 8 years of experience in analytical modeling and numerical computing, Soren oversees the development of high‑performance methods — from spline interpolation and polynomial regressions to multidimensional estimators for real‑world datasets.

Known for his clarity of thought, Soren builds systems that balance mathematical rigor with computational efficiency. He collaborates closely with product, engineering, and UX teams to ensure users get reliable, transparent, and fast results. Outside of work, he contributes to open‑source math libraries and teaches data science workshops at local universities.

Articles: 21

Interpolation Calculator is a mathematical method used to estimate an unknown value between known data points.

Privacy

Disclaimer

Terms

GDPR

Affiliate

Refund

Company

About Us

Contact Us